The turbo-generator fails in operation
Service support - Product "Three Guarantees service" - Common fault handling

Under the correct use and maintenance of the general turbogenerator, it is not easy to fail, but if the use and maintenance of improper, poor environment, disrepair, will also cause failure, the common causes of failure should be analyzed as follows:

 

1) The output voltage of generator is unstable

 

1.1) AVR control (normal when manual control) refer to AVR manual;

 

1.2) Manual or automatic control, it may be due to other mechanical reasons in the system or the prime mover speed is unstable;

 

2) The output voltage is too high, check whether the voltage reading meets the AVR requirements, refer to the AVR manual.

 

3) Generator excitation failure

 

3.1) If the excitation is normal under manual control and abnormal under AVR control, refer to the AVR manual and check the relevant connections;

 

3.2) When there is no excitation current under manual or automatic control, check the circuit between AC exciter and rotating rectifier and AVR, and check whether the lead of rotor coil is open;

 

4) The vibration of the generator is large

 

4.1) Electrical: short circuit or grounding of rotor coil between turns, uneven air gap, deformation and displacement of rotor coil, damage and loosening of insulation of stator core;

 

4.2) Mechanical aspects: the rotor is unbalanced, the center of the generator is not properly matched with the turbine, the gap between the bushing and the shaft is not uniform, the oil is short or the bearing fixing screw is loose, the foundation is not firm, etc.

 

5) The generator rotor moves axially in series

 

5.1) The rotor position is tilted during generator installation;

 

5.2) When the generator is running, the center of the stator and the center of the rotor do not coincide.

 

6) Damage of stator core

 

6.1) When the stator coil is broken down, the silicon steel sheet will be burned;

 

6.2) Loose iron core due to poor manufacturing or rusting.

 

 

7) Fault of stator coil

 

7.1) The loosening of slot wedge or end pad causes insulation wear of winding;

 

7.2) Insulation aging caused by overheating of stator winding due to excessive load or other reasons;

 

7.3) Mechanical damage of winding insulation caused by sudden short circuit;

 

7.4) Breakdown of winding insulation caused by overvoltage;

 

7.5) Insulation damage caused by stator core relaxation;

 

7.6) Poor welding of stator coil joint.

 

 

8) Fault of rotor coil

 

8.1) Insulation resistance drop due to dust accumulation at the end of rotor coil;

 

8.2) The sudden unloading of the generator causes excessive speed of the generator set, resulting in the increase of excitation voltage, which exceeds the voltage of the generator rotor and causes insulation breakdown;

 

8.3) Short circuit between turns of rotor coil or unstable grounding;

 

8.4) Local overheating of the rotor due to unbalanced load or asynchronous operation;

 

8.5) Excessive excitation current caused by generator overload and overheating;

 

8.6) Bad contact of coil joint causes overheating and insulation aging.

 

 

9) Bearing failure

 

9.1) Due to poor insulation between the bearing bush and the shaft, the shaft current passes through the bearing, causing overheating and corrosion of the bearing;

 

9.2) Bearing overheating due to lack of oil;

 

9.3) Bearing oil leakage due to improper oil adjustment and poor sealing;

 

9.4) The bearing center is not aligned, and the bearing bush is scraped.

 

 

10) The cooler is faulty

 

10.1) Cooler pipeline blockage caused by cooling water fouling;

 

10.2) Water leakage and pipe rupture due to mechanical damage, corrosion and vibration of the pipe;

 

10.3) Because the cooling water temperature is too low or because the external inflow of air with too much humidity, resulting in condensation on the surface of the cooler;

 

10.4) Because the inlet temperature of the cooler is too high, the inlet water amount is too small, or the cold and hot air channels are short circuit, the outlet air temperature of the cooler is too high;

 

10.5) Gaskets between the water chamber and the tube plate are aged and not tight.

 

 

11) Overheating of the generator

 

11.1) Overload operation of the generator;

 

11.2) Short circuit of core or winding;

 

11.3) Failure of air cooler or ventilation system.


主站蜘蛛池模板: 国产亚洲精品国产 | 久久久久久亚洲精品不卡 | 亚洲精品无码不卡在线播放he | 欧美性群另类交 | 美女扒开腿让男人桶个爽 | 成人毛片免费视频播放 | 波多野结衣一区在线观看 | 狠狠澡夜夜澡人人爽 | 亚洲视频黄 | 亚洲在成人网在线看 | 成人免费大片a毛片 | 欧美一级二级三级视频 | 日韩精品午夜视频一区二区三区 | 日本三级香港三级少妇 | 特级做人爱c级特级aav毛片 | 九九九在线视频 | 伊人黄色片| 日韩第一视频 | 91精品视频免费 | 中文字幕在线看 | 国产福利久久 | 国产成在线观看免费视频 | 国产精品揄拍一区二区 | 国产玖玖在线观看 | 亚洲黄色性视频 | 日韩欧美高清在线 | 亚洲人成在线播放网站岛国 | 视频一区二区三区自拍 | 性xxxx奶大欧美高清 | 女人张开腿让男人 | 国产精品变态重口在线 | 亚洲 欧美 激情 另类 自拍 | 韩日一级| 亚洲一区二区三区影院 | 国产视频www | 日本特级淫片免费看 | 国产欧美另类性视频 | 97高清国语自产拍中国大陆 | 欧洲成人全免费视频网站 | 国产免费爽爽视频免费可以看 | 日韩高清一级毛片 |